WirelessPointtoPoint-DIGITAL&ANALOGUE-QuickStartGuide–v1.1–June2013 2
 www.qtech.co.nz Tel:033663713
Wireless Point to Point System
WirelessPointtoPoint(WP2P)modulescanbeusedtolinkelectricaldevicestogetherin
situationswherethephysicalseparationorterrainbetweenthemwouldmakedirectwiring
uneconomicorimpractical.
TheWP2Pmodulesincorporatehighspeeddigitalradioswhichhavearangeofuptotwo
kilometres.Themodulesusetheintegratedlowpower900MHzdigitalradiostocommunicate
theirinputstatetotheothermodule.
EachWP2P–DIGITAL&ANALOGUEmodulehastwoswitchinputs,tworelayoutputs,one
analogueinputandoneanalogueoutput.
DigitalI/O
TheWP2Pmodulesoperatebycopyingthestateofeachswitchinputtothecorresponding
relayoutputontheotherWP2Pmodule.Whenaswitchinputisclosed,therelayoutputon
theothermodulewillclose,andwhentheswitchisreleased,therelaywillopenagain.
WP2PModule1
Closeswitchcontacton“INP1”
WP2PModule2
“RLY1”closesoperatinglight
Thedelaybetweenaninputactivatingandthecorrespondingoutputactivatingisnormally
lessthan0.2seconds(seenotes).Withsuchafastresponsetime,theWP2Pdevicescanbe
usedforflowmeterpulseapplications,allowingpulseratesofupto5pulsespersecondtobe
communicated.
AnalogueI/O
TheWP2P–DIGITAL&ANALOGUEoperatesbycopyingtheanalogueinputvaluetothe
analogueoutputontheothermodule.
TheanalogueI/Ocanbeconfiguredforcurrentlooporvoltageoperation.Thefactorydefault
configurationisforcurrentloopoperation.TheanalogueI/Ooperatesoverarangeof0-
20mA,whichmakestheWP2P–DIGITAL&ANALOGUEmodulescompatiblewiththe
industrystandard4-20mArange,whichallowsdetectionofanopencircuitfailure.
TheAnalogueI/Ohas12bitresolution,astatedaccuracyof+/-1%FSD,andissampledata
rateofoncepersecond.
WP2PModule1
Analogue0-20mAsignalinput
WP2PModule2
Analogue0-20mAsignaloutput